4.12.718 ELECTRICAL EQUIPMENT AND WIRING
(1) Electrical equipment and wiring for use in anhydrous ammonia
installations shall be either general purpose or weather resistant as
appropriate.
(2) Where concentrations of ammonia in air in excess of 16 percent by volume
are likely to be encountered, electrical equipment and wiring shall be of a
type specified by and installed in accordance with National Electrical Code
(National Fire Prevention Association 70, ANSI-C1) for Class 1, Group D
locations.
History: Sec. 80-10-503, MCA; IMP, . 80-10-503, MCA; NEW, 1986 MAR p. 1820, Eff. 10/31/86.