37.111.1143    EQUIPMENT ROOM

(1) The equipment room shall be so located that it cannot be entered directly from shower rooms. If entry is gained through the pool or spa deck area, the equipment room must be kept secure.

(2) The recirculation equipment shall be conveniently located for inspection and servicing. Adequate headroom shall be provided above pressure filters.

(3) The floor shall have a minimum slope of 1/4 inch per foot toward the drains with no low spots which would allow the water to stand.

History: Sec. 50-53-103, MCA; IMP, Sec. 50-53-107, MCA; NEW, 1985 MAR p. 782, Eff. 6/28/85; TRANS, from DHES, 2001 MAR p. 2425.